Poor Power Quality Can Plague Process Industry Drives

Power Quality is on the Decline -- Fortunately Variable Frequency Drive Technologies are Available to Help Proceesors Cope

Share Print Related RSS
Page 1 of 2 « Prev 1 | 2 View on one page

W

hile power generation capacity capacity continues to keep up with demand, investment in transmission assets has not kept pace. In fact, investments in transmission assets have been in a steady decline for many years, steadily undermining the grid’s reliability. Consequently, any drop in supply reliability is surely going to impact power quality.

The overall lack of investment has been linked to how energy production and energy transmission is regulated in the U.S. Since its inception, the U.S. power grid has grown as a patchwork of regional transmission networks regulated by local, state and federal authorities. According to Bill Gould, executive director of the Electric Power Research Institute (EPRI) in an ABC News.com interview “The electricity system in this country has operated on the most part on 1950s technology. There are probably lines in cities nearly 100 years old.” Upgrading the aging infrastructure isn’t going to be cheap either—EPRI estimates it’s going to take more than $100 billion to make the necessary improvements.

Ways to Cope Now
But how can processors, and more specifically, plant engineers tasked with specifying or maintaining processing system motors and drives cope with declining power quality—something that’s likely going to be a fact of life for the foreseeable future?

A recent interview with Robert Glickman of ABB’s Electrical Systems Consulting group and Tom Bernhardt, principal engineer within the ABB Inc., Low-Voltage Drives business unit revealed insight into the power quality problems pulse-width modulation (PWM) AC motor control drive technology users are likely to encounter and the design features of this technology that can minimize their effect.

According to Bernhardt any power problem that reveals itself as a voltage, current or frequency deviation and potentially causes equipment failure is a concern to processors. “It’s important to determine the overall impact on a drive, the distance to the fault, and the impedance of the system upstream of the fault.” He says it’s equally important to understand the feeder impedance, the transformer connections between the faulted system and the electrical system bus. Let’s look at each of these conditions:

Voltage Sags
Utility system faults frequently are asymmetrical, single-line-to-ground faults that produce voltage sag, says Bernhardt. Voltage sags are a momentary decrease in rms voltage magnitude for typically ½-30 cycles, or 8 ms-1/2 sec. These sags normally are described by their magnitude and duration. But they also need to be understood in terms of the voltage imbalance, non-sinusoidal wave shapes and phase-angle shifts that accompany them.
“AC drives have considerable capability to ride through a voltage sag, because they store energy on their DC bus capacitors and can make use of the energy stored in the load’s inertia. The drive’s line voltage is monitored at the DC bus. Its control logic and fan power is taken from that bus. Therefore, the drive is independent of line voltage sag as long as the dc bus holds up. The DC bus typically will trip on under-voltage at an equivalent line voltage of 65- 51% of nominal rated voltage.”

On its own, explains Bernhardt, the DC bus can deliver full power to a load for about one cycle or 16 ms by allowing itself to decrease from its nominal voltage. As the bus voltage drops, the drive regulator adjusts the PWM pulse width to make up for the reduced magnitude of the output voltage waveform of the inverter. Alternatively, the drive could allow the motor speed to decrease and use the energy stored in the inertia of the load to maintain bus voltage. Typically, more energy is stored in the load’s inertia than the DC bus, making it possible to hold bus voltage for a longer duration--approximately ½-5 sec. says Bernhardt.

Wye-Delta Transformers
Both Bernhardt and Glickman point out that transformer connections have an interesting effect on the ultimate line voltage seen at the load during an asymmetric fault. Most AC drives are fed from a three-wire delivery without a neutral. As a result, the input rectifier stage only sees line-to-line voltages. At the fault location, a single-line-to-ground fault will yield a voltage of zero on one phase to neutral voltage, but the other two phases are essentially unaffected. If a wye-delta transformer is between the fault and load, then two of the phase voltages on the delta side affected by the fault go to zero, but none of the line-to-line voltages go to zero. The drive will see a voltage sag on two of the line voltages. Similarly, a line-to-line fault will cause phase shifting and can cause a zero voltage condition on the secondary of a transformer.

Phase Imbalance The phase imbalance that is associated with voltage sag is caused by the difference in the inductive reactance to resistance (X/R) ratios of the source and the faulted feed, and by the propagation of voltage sags due to single-phase faults through a transformer.

During normal operation, the input voltage to a drive is balanced and the diodes in the bridge rectifier are symmetrically forward-biased. A phase imbalance acts to lower the magnitude of one or more line-to-line voltages, reducing the peak voltage for one or more phases below the nominal capacitor voltage. This causes the rectifier diodes not to forward bias. In this state, no energy flows from the AC mains to the capacitor. The capacitor will continue to discharge until there is an input voltage peak that is high enough to forward-bias the diodes.