Special rules for tuning level controllers

Loss of level controls can kill a process in a heartbeat, so tuning them properly should be a priority. F.G. Shinskey reports on the different tuning rules that apply to level loops based on vessels being regulated.

Share Print Related RSS
Page 2 of 2 1 | 2 Next » View on one page


With a linear proportional controller, the steady-state level is linear with steady-state flow. With one of these nonlinear controllers, the steady-state level will remain in the middle of the tank over only a narrow range of flow, for the most part settling above or below the low-gain range, where the controller gain is higher than that of a linear controller at the same flow. Therefore, their use is counter-productive, and they have been removed from service in most cases where they have been tried.

Only if the flow has a very narrow probability distribution about a known operating point, with the low-gain zone of the controller centered around it, is the nonlinear proportional controller useful. However, these characterizers can be of some help to a PI level controller, as described later.

Material-Balance Regulators
The most common use of level controllers is to regulate the material balance between interconnected stages of a process. For example, a multi-effect evaporator has a level controller manipulating flow from one effect to the next, and from the last effect to the product tank. Most distillation columns have two level controllers–one at the base of the column or in its reboiler, manipulating bottom-product flow, and one at the reflux drum, manipulating distillate or reflux flow. They are scattered through any process plant, essential to its operation, and must be in service before the plant can start.

Here again, there may be no economic penalty for deviation from setpoint, but overflow and emptying must be avoided. As in a surge tank, rapid changes in manipulated outflow are undesirable, but these vessels have shorter time constants–in the range of 20 seconds to 5 minutes. Proportional control may not be acceptable, and there may be an optimum setpoint, designed to keep reboiler tubes covered for example. The level measurement may also be very noisy due to agitation or boiling, and the noise should not be passed along to the manipulated flow.

Proportional-Integral Control
The maximum rate-of-change of manipulated flow is still governed by Equation (4), but the addition of integral action to the controller forms a second-order system, even in the absence of additional dynamics. Its damping factor varies with both controller settings. 

Damping factors have been fixed at values of 0.5 and 1.0 by the integral settings of 0.5 and 2 respectively, the proportional band being 50 % for both cases. They represent reasonable limits: the value of 1.0 represents critical damping (no overshoot) and 0.5 has some overshoot. Lighter damping is not particularly desirable in a level loop.

The selection of proportional band needs to be made on the basis of maximum rate-of-change of flow, or of peak level deviation for a given load change. The effect of changing proportional band on the step load response where  has been fixed at 0.5 by setting the integral time is a function of the proportional band. 

Observe that the proportional setting determines the peak deviation for a given damping factor. However, the amount which the manipulated outflow overshoots the inflow step is independent of proportional band. The time of occurrence of the peak level deviation is determined entirely by the integral setting, and that of the peak change in outflow is exactly double that value. Peak deviation is ep and peak change in outflow is )mp.

Select a desired damping factor, then estimate the largest expected load step and the acceptable peak deviation resulting from it. Then calculate the proportional band required to satisfy this relationship. 

Where f(.) is the coefficient in the third column of the table. As an example, consider a desired damping factor of 0.707, with a load step of 30 % resulting in a peak deviation of 20 %: P = 100(20/30)/0.66 = 100%. Then I = 2 (100/100) = 2.

Additional dynamics in the loop have little effect, up to a limit. For example, a loop with 0.707 can tolerate a dead time up to 0.2 I with no loss in damping and only a small increase in the maximum rate-of-change in outflow; the dead time must be as high as 0.5 I to approach the limit of stability. Inserting a first-order lag of 0.4 reduces the maximum rate-of-change of manipulated outflow by the same 0.65 factor as in proportional control, but causes the peak deviation and overshoot in manipulated flow to increase by half, as well as extending the settling time. Filtering up to this point does not destabilize, but its effects should be limited to noise reduction.

References
1. Wade, H.L., Basic and Advanced Regulatory Control: System Design and Application, 2nd ed., ISA, Research Triangle Park, NC, 2004, pp. 168-169.

2. Shinskey, F.G., “Taming the Shrink-Swell Dragon,” Control, March 2004, pp.35-40.

 

 


F.G. (Greg) Shinskey, process control consultant, has more than 34 years experience as a systems engineer. He is author of several textbooks on control systems design and is based in North Sandwich, N.H. Contact him at shinskey@ msn.com.

 