Interested in linking to "It's the Resolution, Stupid! Part 2"?
You may use the Headline, Deck, Byline and URL of this article on your Web site. To link to this article, select and copy the HTML code below and paste it on your own Web site.
08/21/2005
The consequence of this is a large value for the controller gain. With a measured variable span of 20°C, the value of the controller gain of 5%/% would be a reasonable value for a temperature controller. But with a measured variable span of 100°C, the value of the controller gain would be 25%/%. Such large values for the controller gain are occasionally encountered in control loops, and in most cases, this is the result of a measured variable span that is wider than required for control.
In any loop with a large value for the controller gain, careful attention must be paid to the resolution. Consider the following for a temperature control application:
The smallest change in the measured input is 0.1°C, which is 0.1% of the input span of the measured variable. With a controller gain of 25%/%, a change of 0.1°C in the temperature would cause the controller output to change by 2.5%. In reactor temperature control applications, this is likely to attract some attention. Figure 1 illustrates the performance of a PI controller for a disturbance to a temperature loop. The resolution on the temperature measurement is 0.1°F, which is 0.1% of the measurement span of 100°F. With a controller gain of 2.6%/%, a temperature change of 0.1°F (also 0.1% of span) causes the controller output to change by 2.6%. Such abrupt changes are clearly visible in the controller output, but otherwise the resolution has little impact on the performance of the loop.
However, the impact of the resolution is much greater on the performance of the PID controller illustrated in Figure 2. The addition of derivative has reduced the maximum departure from set point (150°F) from 2.3°F with PI to 1.2°F with PID, which in applications such as reactor temperature control is very appealing. The tuning coefficients are reasonable:
However, there are numerous distinct "bumps" in the controller output. It is also evident from Figure 2 that the bumps are associated with 0.1°F changes in the temperature. The controller has a derivative mode smoothing factor of 0.1 (which is a derivative gain limit of 10).
The following changes will reduce the"bumps," but at the expense of performance:
The latter is the only viable approach.
Traditional installations relied on current loop inputs. If an A/D converter with a resolution of 1 part in 4000 is applied to a current loop input with a span of 100°F, the resolution in engineering units is 0.025°F. The performance of the PID controller is illustrated in Figure 3. The bumps are still present, but they are much smaller.
The customary industrial practice with A/D converters gives resolutions such as the following:
There are a number of other factors that go into the decision as to which approach to use. But for purposes here, let's consider the resolution to be 1 part in 4000 for an input range of 4 to 20 ma.
A number of inexpensive modules are available that convert the input from a thermocouple or RTD to a 4 to 20 mA signal. Most of these products provide linearization and, for thermocouples, reference junction compensation. The measurement range on these modules often reflects the characteristics of the sensor. Consequently, for a type J thermocouple, the lower range value is often -200°F and the upper range value is 1320°F. The resolution of this input is

This is not as good as the input module that provides the input value as the temperature in °F to 0.1°F. To obtain better resolution, a narrower span is required for the module that produces the milliamp signal.
Another input application where the resolution must be examined carefully is for inputs from weight transmitters or load cells.
Modern load cells have very high resolutions. For example, a weight of up to 6,000 kg can be indicated to 0.1 kg. This measurement has a resolution of 1 part in 60,000!