It's the Resolution, Stupid! Part 2

Resolution Is More Important Than Most People Think. Read On to Find Out Why.

Share Print Related RSS
Page 3 of 4 1 | 2 | 3 | 4 View on one page

A number of inexpensive modules are available that convert the input from a thermocouple or RTD to a 4 to 20 mA signal. Most of these products provide linearization and, for thermocouples, reference junction compensation. The measurement range on these modules often reflects the characteristics of the sensor. Consequently, for a type J thermocouple, the lower range value is often -200°F and the upper range value is 1320°F. The resolution of this input is

Equation 1

This is not as good as the input module that provides the input value as the temperature in °F to 0.1°F. To obtain better resolution, a narrower span is required for the module that produces the milliamp signal.

Another input application where the resolution must be examined carefully is for inputs from weight transmitters or load cells.

Modern load cells have very high resolutions. For example, a weight of up to 6,000 kg can be indicated to 0.1 kg. This measurement has a resolution of 1 part in 60,000!

Suppose this weight is provided via a 4-20 mA signal to an input module with a resolution of 1 part in 4000. A change of 1 "count" in the raw value would result in a change in the indicated weight by 6000.0 kg / 4000 = 1.5 kg. The weight indicated by the digital system would not generally agree with the weight indicated at the load cell.

In order that the weight indicated by the digital system agree exactly with the weight indicated at the load cell, approaches such as the following have to be used in lieu of current loop inputs:

  1. The input from the load cell is provided as a BCD (binary coded decimal) value. Each digit displayed at the load cell is sensed by the digital system via four discrete inputs. A 4-digit display requires 16 discrete inputs; a 5-digit display requires 20 discrete inputs. In addition to the obvious requirement of lots of discrete inputs, there are distance limitations and grounding issues. In the past, this approach was quite common in PLC installations, mainly because similar approaches were used for inputs for thumb-wheel switches, outputs to panel-mounted digital displays, etc. But as panels are being replaced with CRT-based operator stations, this approach is rapidly losing its popularity.
  2. The input from the load cell is provided via a serial communications interface. The weight is generally transmitted as a sequence of printable characters that can be converted by the digital system to an engineering value. There are no effective standards for such interfaces, so custom software is usually required within the digital system to process these inputs. Another issue arises in plants with a large number of load cells or weight transmitters. If the digital system can accept a large number of serial inputs, a separate input can be provided for each load cell. Where the number of serial inputs is limited, a multi-dropped configuration is required where more than one load cell can be connected to each serial link. The digital system must now "poll" the load cells on each serial link, which complicates the software that communicates with the load cells. These and other problems with serial links are sources of headaches, but with this approach the value indicated by the digital system agrees exactly with the value indicated by the load cell.
  3. The future direction appears to be with network interfaces such as Profibus. The requirements for such interfaces have been agreed upon, which imposes some discipline on the manufacturers of load cells (with serial communications, they were free to go their own way and change whenever they liked). Large numbers of load cells can be accommodated over such networks, and they can be mixed with other measurement devices (in the case of a Profibus network, anything that has a Profibus interface). Those with past experience in digital technology are skeptical of all "how great it's going to be" scenarios. However, this is clearly the direction of the future.

Resolution for Outputs

In PLC installations, a common approach is to represent the output as an integer value to either 1% or 0.1%. An output value of 0% is represented as 0; an output value of 100% would be represented as either 100 (to 1%) or 1000 (to 0.1%). One advantage of this approach is that the output value can be represented on a graphical display with little or no need for conversion calculations within the graphical display (it only needs to know where to put the decimal point).

If the output value is represented to 1% (output range is 0 to 100), the resolution is 1% or 1 part in 100. Certainly there are valves that cannot be positioned to within 1%, but most can. Any variable speed drive can certainly respond to smaller changes than 1%.

If the output value is represented to 0.1% (output range is 0 to 1000), the resolution is 0.1% or 1 part in 1000. This is beyond the capability of valves installed in industrial facilities. Variable speed drives can probably do better, but 0.1% would be adequate for most applications.

In some PLC applications, a similar approach is used for the set point for the inner loop of a cascade. The output of the controller is expressed in the engineering units of the measured variable for the inner loop. For example, if the inner loop is a flow controller with a range of 0 to 20.0 kg/min, the output would be converted to kg/min and stored as an integer value to 0.1 kg/min. That is, 0 is 0 kg/min and 200 is 20.0 kg/min. The resolution is 1 part in 200.

A similar approach is used for the measured input for the inner loop. Even if the source of the input is a current loop, the raw value from the input module is converted to engineering units in kg/min and represented to 0.1 kg/min. This permits the value for the measured variable to be readily presented on a graphical display. However, flow measurement devices such as Coriolis meters, magnetic flow meters, vortex shedding meters, etc., are capable of far better resolutions.