How to select control valves, Part 3

When it comes to selecting and sizing control valves, gain and stability are key characteristics. The non-commercial valve selection chart in this article serves as a reference tool you can download!

Share Print Related RSS
Page 1 of 2 « Prev 1 | 2 View on one page
Béla LiptákBy Béla Lipták, Contributing Writer

 

In the search for the most appropriate control valve, gain and stability are as crucial as any other selection characteristics. The gain of any device is its output divided by its input. The characteristic range and gain of control valves are interrelated. The gain of a linear valve is constant. This gain (Gv) is the maximum flow divided by the valve stroke in percentage (Fmax/100 %).

Most control loops are tuned for quarter-amplitude damping. This amount of damping (reduction in the amplitude of succeeding peaks of the oscillation of the controlled variable) is obtained by adjusting the controller gain (Gc = 100/%PB) until the total loop gain (the product of the gains of all the control loop components) reaches 0.5 (see Figure 1 below).

 

 

RELATED ARTICLES

    

>>How to select control valves, Part 1
>>How to select control valves, Part 2


The gains of a linear controller (Gv = plain proportional) and a linear transmitter (if it is a temperature transmitter, its gain is Gs = 100%/°F) are both constant. Therefore, if the process gain (Gp = °F/GPM) is also constant, a linear valve is needed to maintain the total loop gain at 0.5 (Gv = 0.5/GvGcGs = constant, meaning linear).

If the transmitter is nonlinear, such as in the case of a d/p cell (sensor gain increases with flow), one can correct for that nonlinearity by using a nonlinear valve whose gain drops with flow increases (quick opening). In case of heat transfer over a fixed area, the efficiency of heat transfer (process gain Gp) drops as the amount of heat to be transferred rises. To compensate for this nonlinearity (drop in process gain = Gp), the valve gain (Gv) must increase with load. Therefore, an equal-percentage valve should be selected for all heat-transfer temperature control applications.

 

FIGURE 1: WELL-TUNED LOOPS

    

Well-tuned Loops  

In a properly tuned loop, the decay ratio of the oscillation amplitude is constant at 0.25. Such decay ratio (¼) is obtained if the product of the component gains (the total loop gain) is constant at 0.5.

In case of flow control, one effective way of keeping the valve gain (Gv) perfectly constant is to replace the control valve with a linear cascade slave flow control loop. The limitation of this cascade configuration (in addition to its higher cost) is that if the controlled process is faster than the flow loop, cycling will occur. This is because the slave in any cascade system must be faster than its master. The only way to overcome this cycling is to slow down (detune) the master by lowering its gain (increasing its proportional band), which in turn degrades its control quality. Therefore, this approach should only be considered on slow or secondary temperature control loops.

Positioning Positioners
A valve positioner is a high-gain (0.5% to 10% proportional band), sensitive, proportional-only, valve-stroke position controller. Its set point is the control signal from the controller. The main purpose of having a positioner is to guarantee that the valve does in fact move to the position that corresponds to the value of the controller output.

The addition of a positioner can correct for such maintenance related effects as variations in packing friction due to dirt buildup, corrosion or lack of lubrication; variations in the dynamic forces of the process; or nonlinearity in the valve actuator. In addition, the positioner can allow for split-ranging the controller signal between valves, or can increase the actuator speed or actuator thrust by increasing the pressure and/or volume of the actuator air signal. In addition, it can modify the valve characteristics by the use of cams or function generators.

A positioner will improve performance on most slow loops, such as the control of analytical properties, temperature, liquid level, blending, and large-volume gas flow. A controlled process can be considered “slow” if its period of oscillation is three or more times the period of oscillation of the positioned valve.

Positioners also are useful to overcome the “dead band” of the valve, which can be caused by valve-stem friction. The result of this friction is that whenever the direction of the control signal is reversed, the stem remains in its last position until the dead band is exceeded. Positioners will eliminate this limit cycle by closing a loop around the valve actuator. Integrating processes, such as liquid level, volume (as in digital blending), weight (not weight-rate), and gas-pressure control loops are prone to limit cycling and will usually benefit from the use of positioners.

In the case of fast loops (fast flow, liquid pressure, small-volume gas pressure), positioners are likely to degrade loop response and cause limit cycling, because the positioner (a cascade slave) is not faster than the speed at which its set point (the control signal) can change. A controlled process is considered “fast” if its period of oscillation is less than three times that of the positioned valve.