The same is true for ultrasonic flow measurement. Wouldn’t it be great if you could clamp a sensor onto the pipe and measure the flow through the pipe? Benefits would abound—including not having to shut down the flow or cut the pipe. Installation would be faster and easier. Unfortunately complications tend to get in the way of this smooth-flowing scenario.
Ultrasonic flowmeter technology falls into two general categories—Doppler and transit-time. Early ultrasonic flowmeters used the Doppler effect to measure flow because Doppler signal processing techniques were more readily adaptable to the analog technology of the time. The development of transit-time ultrasonic flowmeters accelerated as microprocessor technology became more prevalent and cost-effective. Now only a handful of ultrasonic flowmeter designs currently use Doppler technology exclusively.
The Doppler Effect
ADVERTISEMENT
The Doppler effect is characterized by a frequency shift that occurs when an object is moving towards or away from an observer. For example, an ambulance siren will sound differently when the ambulance is approaching an observer from when it is moving away. When the ambulance is moving closer, the waves emitted by the siren will tend to be closer together and, therefore, have a higher pitch (frequency). The frequency shift is proportional to the speed with which the ambulance is moving closer.
![]() |
Figure 1. A small ultrasonic flowmeter with two traverses.
|
Transit Time
Transit-time ultrasonic flowmeters measure the amount of time the ultrasonic signal takes to travel upstream and downstream in the fluid. With no flow, these times are the same. In a flowing fluid, the ultrasonic signal will travel faster in the downstream direction. The fluid velocity is determined by analyzing the measured upstream and downstream transit times. Transit-time ultrasonic flowmeters mitigate the need for particles in the fluid. However, these flowmeters will not function when the ultrasonic path is broken because a fluid is excessively opaque to ultrasonic energy.
Some correlation flowmeters could be considered ultrasonic flowmeters because they use ultrasonic energy to sense the flow stream at two or more locations in the pipe. The distance between the locations and signatures are correlated to determine the fluid velocity.
![]() |
Figure 2. A transit-time ultrasonic flowmeter.
|
Ultrasonic flow measurement may sound straightforward, but there can be a number of complications. For example, how many and what type are the particles in the fluid? If there are too few particles, then the reflected signal may not be strong enough to process. If there are too many particles, then the measured velocity may measure the fluid velocity at the pipe wall and not represent the average velocity in the pipe. A distorted velocity profile also can adversely affect the measurement.
Ultrasonic flowmeters measure fluid velocity—not flow. Users want to know the flow rate—not the velocity. This may appear to be a subtle point because the flow can be calculated by multiplying the measured velocity times the cross-sectional area of the pipe. However, flow measurement accuracy can be affected by the uncertainty associated with the cross-sectional area. Some ultrasonic flowmeters have spool pieces that are tested in a flow laboratory to ensure a known relationship between the measured velocity and flow. Other ultrasonic flowmeters consist of a pair of sensors that the user attaches to the outside of pipe where the inside diameter and internal condition of the pipe may not be known accurately. In such an installation, the accuracy of the flow rate is questionable, even if the sensors can measure velocity with no error.
Ultrasonic flowmeters are available for pipe sizes range between approximately 6 mm and 10 m in diameter. Fluids include liquids, gases and multi-phase fluids, such as slurries. Ultrasonic flow measurement techniques can be used to measure the velocity of stack gas and flare gas. In general, sensors can be wetted or non-wetted (clamp-on). Wetted sensors tend to exhibit better ultrasonic connections with the fluid while clamp-on sensors are easier to install.
![]() |