Orifice Rangeabilty; Bubblers for Difficult Service

ControlGlobal.com

Our Readers Ask and We Answer. How to Choose Suitable Flowmeters? Who Is Interested in the Loop Slooth? How to FIx My Bubbler Application Plugging Problems?

“Ask the Experts” is moderated by Béla Lipták, process control consultant and editor of the Instrument Engineer’s Handbook (IEH). Preparation of the 5th edition of the handbook requires three co-editors. If you are interested, send in your resume. To ask a control question or to join our team of experts answering the questions in this column, write to liptakbela@aol.com.

Q: I am trying to choose a suitable flowmeter to measure the flow rate of argon gas. I received a data sheet for one that appears very strange to me. The data sheet says that the flow element was an orifice, and the limits of flow were from 5 Nm3/h to 280 Nm3/h!!! The operating pressure was 21 barg. We are not using the orifice plate flowmeter for this application because its rangeability is only 3:1. I have looked for a flowmeter to cover this large range (56:1), and so far no success! Would you please help me in this regard?

ADVERTISEMENT

info@nirooresan.com

A: The flow measurement range of a conventional orifice-dp cell combination is limited to 3:1. Intelligent dp cells can switch their range to achieve a rangeability of 10:1, but in most designs, the error in percent of actual flow will increase as the flow drops. A more accurate reading is obtained if, instead of range switching, you place two d/p cells on the same orifice, a high- and a low-range one.

If you need a range that exceeds 10:1, you can use several parallel pipe runs of different sizes and open or close as many runs as needed to keep the actual flow always between say 50% and 90% of the maximum flow in the active runs.

My choice for this high-pressure gas flow application would not be to use orifices at all. For a > 50:1 range, I would use one or preferably two Coriolis meters in parallel. If at low flows, you can live with an error of about 5%, one Coriolis meter is enough. Other high- rangeability flowmeter options include thermal (20:1), turbine (10:1), utrasonic (10:1), and vortex (10:1).

Béla Liptak

Q: We have a bubbler application that has a plugging problem. We have tried various configurations of the tip to reduce the plugging—angled, notched, etc., with little relief.

I remember that many years ago in another difficult application another engineer used a dip-tube diaphragm. I believe there were separate diaphragms on the high and low sides, and that the diaphragms had very small holes. There was a very light purge, on the order of 1 SCFH or less, through a dp regulator for each side. This was very successful.

Unfortunately, that engineer is no longer with us. Now I’m working for another company, and nobody at that plant can remember where the diaphragm was purchased.

Both applications are not pressure vessels. The new application runs at 20-25 psig.
Can you recommend some vendors for this application?

Jim Becker
Bayer MaterialScience
james.becker@bayerbms.com

A: Is the questioner referring to the PMC 1:1 pneumatic repeater design (www.pmc1.com), which I have previously modified to build a submersible variation to replace bubbler tubes?  PMC now makes an electronic dipstick version. The same folk also make submersible electronic transmitters. PMC does have a pneumatic dip tube replacement as a standard product. 

These units were originally built for the pulp and paper industry (PMC was once the Paper Machinery Company), but I have found them handy in mineral processing units over the years.

Ian H. Gibson
Engineering Consultant
Process, Control and Safety Systems

A: A prominent cause of plugging of bubble tubes is dehydration of the solution or slurry in the vessel by the purge gas. One solution is to hydrate the purge gas in another bubbler of clear solvent before it enters the main bubbler. Another possibility is the use of a liquid purge.

Greg Shinskey
Process Control Consultant
Wolfeboro, NH 03894

A: I do not know where you can get diaphragms such as the ones you mention.

In my experience, however, the smaller the bubble orifice and/or purge rate, the easier it is to get plugging. Large-diameter orifices (I have seen 6-in. diameter bubble pipe tips) are often used in wastewater wet wells with good results. It may take a while for the expanded section to fill and equalize if the purge gas is stopped or the bubbler end uncovered, but the large orifice did work pretty well.

I do remember once seeing a bladder-type pressure sensor setup, but I do not remember the manufacturer.
I will also mention that notches in a bubble pipe tip are often used to make the bubbles release in the best spot with regard to error from liquid moving past the orifice.

Al Pawlowski, PE
ALMONT Engineering
Baton Rouge, La., U.S.

A: It is well-known that plugging problems decrease as the square of the diameter of the dip tube. The problem writer gave no information as to the cause or definition of plugging in his application.