"Ask the Experts"is moderated by Béla Lipták, process control consultant and editor of the Instrument Engineer's Handbook (IEH). The 4th edition of Volume 3, Process Software and Networks, is in progress. If you are qualified to contribute to this volume, or if you are qualified to answer questions in this column, or want to ask a question, write to liptakbela@aol.com.
Q: We would like to improve on the safety record of fossil and nuclear energy processes in our design of a new renewable energy process. One element of that improved performance is the selection of the safe failure position for valves. We followed the advice in your handbook on designing for mechanical, plant or instrument air and electric power supply failures. We also followed your advice on safe failure positions, such as valves being closed on heating and open on cooling. In critical cases, we are also using redundant valves with different actuators—one pneumatic and the other an electric motor—and then installing them in parallel for cooling and in series for heating applications, as you suggested.
ADVERTISEMENT
Now, we came across a situation where the safe failure position changes with the phase of the process, and depending on the phase, it can be open, closed or the last position. Am I right that in such cases we should use double-acting and not spring-return actuators? Do you have any other advice on how to design for such situations?
George Scott
solarH2cell@aol.com
A: Your options are a function of how much you can afford to spend versus what level of safety you require. In any case, you should have backup for both your air and electric power supplies.
The less expensive solution is to use a double-acting valve with redundant solenoids to load one side or the other, or vent both as the required failure position changes.
The more expensive choice is to provide three parallel pipe runs with block valves, and select the right run for each phase of operation. If the switching needs to be fast, the block valves should be automatic.
In either case, all valves should have limit switches and the logic to make sure that valve status and operating mode requirements match.
Béla Lipták
answeremail@putman.net
A: It is not unusual to have valves with both fail-open and fail-close control systems in fossil power applications. This arrangement is usually achieved through the use of two solenoids, one for fail closed and one for fail open.
The reliability of these systems can be further improved by using redundant solenoids and a voting system, or by specifying the reliability of the instruments using IEC 61508 and the SIL rating system. Triple-redundant solenoids have been used for more than 30 years in Europe for boiler and condenser protection. Triple redundancy is being replaced by the SIL system.
Stephen Freitas
sf@ccivalve.com
A: Without knowing nearly enough about the process you are using, two ways to accomplish your stated goal come to mind.
Have you done the probability analysis for everything involved in a failure, not just the air supply? Doing so would be a good idea. There is a balance between cost and risk to be considered. Intrinsic electrical safety is based on the idea that the probability of two improbable events happening at the same time is an acceptable level of risk. Is it possible in this application for one accident or fire to take out both plant air and electricity?
Bill Hawkins
bill@iaxs.net
Q: Below is a question about an ammonia storage tank:
We need a level transmitter with an accuracy of ±1 mm. The transmitter would be installed on the roof of tank on an 8-in. nozzle on the top of the tank. I don't know which to use—servo LT or guided wave radar? What are the benefits and limitations of each?
Mina Movahedinia