Sensible Sensor Speed-Part 2

Greg McMillan and Stan Weiner Continue Their Conversation on Sensor Speeds

Share Print Related RSS
Page 1 of 2 « Prev 1 | 2 View on one page
This article was printed in CONTROL's June 2009 edition.

McMillan and WeinerBy Greg McMillan and Stan Weiner

Greg McMillan and Stan Weiner bring their wits and more than 66 years of process control experience to bear on your questions, comments, and problems.
Write to them at
controltalk@putman.net.

Stan: In the old days, the deadband of mechanical components and the transmission lag of pneumatic devices added time delays to loops that would be unacceptable by today's standards. Fortunately, we didn't have auto tuners and data historians back then, so we didn't realize the pathetic response and repeatability of these measurements. The Bourdon tubes, bellows and linkages of these measurements belong in a really scary exhibit along with pictures of us with big mustaches and bellbottoms.

Greg: Now we have smart microprocessor-based measurements, such as Coriolis mass flowmeters, coplanar pressure and differential pressure transmitters, and radar level, whose installed accuracy is 50 times better than what we worked with in the 1960s and 1970s. Their accuracy approaches the uncertainty in calibration standards. The drift is so small the average instrument engineer will have changed jobs or retired before the device needs a calibration check. The response is so fast the measurement time constant is too small to be measured in a DCS. The decision to use these instruments is a no-brainer if one considers the reduction in lifecycle costs, the elimination of wild goose hunts, and the possible process control improvement and optimization opportunities.

Stan: The way I insured that a project's budget wouldn't prevent me from doing what was best was to spend what was estimated, and I was able to use the state of the art particularly in flow measurements. The main sources of uncertainties, maintenance headaches and poor response are sensing lines (impulse lines) and sample lines. I was on a mission to go with in-line measurements.

Greg: I recently reread a 1992 InTech article, "Gas-Purged DP Transmitters for Liquid Level and Flow," that gave technical details on how to keep sensing lines at a known composition and state. Purges are designed to keep sensing lines from plugging, trapping process fluids, or collecting vapors or condensation. Liquid purges can adversely affect the process composition, so the use of gas purges was studied. It was found that a sudden increase in process pressure can cause the process to backfill the sensing line or dip tube with process fluid. The result is a compression of the gas in the line or tube and a bump in measurement indication. The pressure and flow or level indication does not return to normal until the gas purge flushes out the process fluid. The solution would seem to be to just crank up the purge rate, but a high purge rate can create an appreciable pressure drop in the sensing lines and increase the cost of the purge gas, which in many cases is nitrogen, and the cost of the vent system in large projects. The size and duration of the bump in the measurement indication makes the 200-msec response time and 0.02% repeatability of the differential pressure transmitter a wasted opportunity.

Stan: We've managed to take 21st-century technology, and degraded the performance to 1970s and 1980s levels using old installation practices.

June 2009 Comic

Greg: RTD sensors have a repeatability of 0.1 °C and a drift of less than 0.04 °C per year, yet you see installations with insufficient immersion lengths that are measuring jacket or ambient temperature. The most flagrant example is the temperature measurement of structured packing in columns. Nearly all distillation columns, strippers and absorbers built in the last 10 years use structured packing instead of trays. In the good old days of trays, we had plenty of room for an immersion length at least 10 times the diameter, and a rule of thumb to insure the conduction error from heat loss from the tip along the thermowell wall to the flange was negligible. The new packing is as thin as foil, and an attempt drill a hole for a thermowell creates a jumbled mess. Bare RTD sensing elements are used to reduce thermal conduction error, but since their tips don't extend past the interior wall, you're most likely measuring nozzle temperature rather than process temperature. I'd expect a lot of the separation efficiency gain from going to packing is lost from monitoring and controlling unrepresentative temperatures.

Stan: The primary time constant of a bare RTD element varies from about 4 to 10 seconds, depending on manufacturer and model number. The time constant of an RTD in a thermowell varies from 25 to 100 seconds, depending on fit and fluid velocity. For a tight fit (0.01-inch clearance between the element and the inside diameter of the well), the limitation to response speed is the process's convective heat transfer coefficient that depends on the fluid velocity. Thermocouples are said to be faster, but once installed in the thermowell, the difference is masked.

Greg: In an analogous fashion, the damping setting on a transmitter or the signal filter in a DCS should be set just large enough to keep the controller output fluctuations within the resolution limit of the control valve, so it doesn't react to noise.