Maximizing Control-Loop Performance

Tune Your Processes to Stop Giving Away Valuable Commodities

Share Print Related RSS
Page 1 of 4 « Prev 1 | 2 | 3 | 4 View on one page

By F. Greg Shinskey, Process Control Consultant

Motor gasoline is blended at the refinery to specifications that include octane rating, typically grades of 87 and 93 octane; at the pump these may be further blended to produce an intermediate grade such as 89 octane. An engineer I met was especially proud of how well octane number was controlled at his refinery—but he always filled his car at a competitor's station, although the price per gallon was the same. His rationale was that the competitor's control over octane number was more variable, but still had to meet the minimum standard of 87 for regular grade—hence its average octane rating was higher by that variability. The competitor's refinery was giving away octane, and he was willing to accept it. The analysis below can be used to describe the cost of giving away any valuable ingredient, or any operating cost associated with the variability of control.

Safe-Side Variations

The cost to the refinery in excess octane giveaway is a direct function of its variability, with two possibilities shown in the step-load response curves of Fig. 1. The upset could either drive the controlled variable in the "safe"direction shown in the black curve, or the "unsafe"direction, shown in red. Here, "safe"is meant to infer that the controlled variable is driven toward the favorable side of the specification limit, in this case above the 87-octane specification. Safe-side variations do not require any action either by the operator or any automatic response, because product specifications are not thereby violated. (Although there is a slight overshoot of setpoint on the return trajectory and therefore a momentary violation, any downstream capacity at all would absorb this brief transient, and it would not appear in the final product.) Safe-side variations simply result in an economic loss that is quantifiable.

If the setpoint in Fig. 1 is also the specification limit, and the measured octane rating rises due to the upset before returning to setpoint, the octane giveaway is related to the integrated error of the controlled variable from setpoint. Integrating this deviation or error e between controlled octane and its setpoint over time t gives the Integrated Error IE in terms of octane-minutes. Subsequent multiplication by the current product flow rate in gal/min yields octane-gal given away during that interval. Multiplying that result by the cost difference in the dollars/gallons/octane number converts the integrated error into dollars lost.

The cost function may not be linear. For example, the price difference at the pump between 87 and 89 octane, and between 89 and 93 octane may both be $0.10 per gallon, which probably reflects market forces rather than production cost. Nevertheless, small variations in the function around a given specification can be assumed to be linear, allowing IE to be a useful criterion in evaluating the cost of poor control.

When using PI or PID control over any variable, integrated error is directly related to the size of the disturbance and the controller settings. The ideal PID controller is simply represented in Eq. (1):

Equation 1

where m is the variable manipulated by the controller, and P, I and D are its proportional band in percent and integral and derivative time settings respectively. This formula may be evaluated both before and after an upset, when the deviation e and its time derivative are both zero. If the controller output has changed between those two steady states, there will be an integrated error:

Equation2 & 3

Equation (3) applies equally to interacting and non-interacting PID controllers and PI controllers as well. There are some obvious conclusions to be drawn from it: To minimize the cost associated with IE, minimize the feedback control effort Δm required to respond to an upset (by using feedforward), and reduce the P and I settings (without sacrificing stability).

Unsafe-Side Variations

When the controlled variable wanders to the unsafe side of the specification limit, decisions have to be made. In failing to meet requirements upon which the product is to be sold, it must be set aside for blending with better-than-acceptable product, rejected to a less-valuable use or rerun. All of these operations are costly and cause disruptions affecting production rate. Operators avoid them if at all possible.

The alternative is to adjust the setpoint of the composition controller so that it exceeds the specification limit by the expected variations in quality under all but the worst cases. This is also costly in that it results in quality giveaway all the time. Yet this is the normal condition of most product-quality controllers in most plants, and offers the largest economic potential for tighter control in processing plants universally. To minimize giveaway in the face of unsafe-side variations, the amplitude of those variations must be minimized.

The curves in Fig. 1 are typical of a loop responding to a step change in load—the flow or composition of one of the ingredients entering the process—and the subsequent reaction of a well-tuned PID controller to that upset. A step was selected as it is the most difficult disturbance for a control loop, containing all the frequencies from zero to infinity—a step has the same power spectrum as white noise. At the zero-frequency end, it requires a permanent change in controller output, necessitating integration. At the other end, its rise time is zero, requiring vigorous proportional and derivative action. Finally, it is commonly encountered when equipment trips or is suddenly switched, and is the easiest test to administer. In their monumental work on controller tuning in 1941, Ziegler and Nichols used a pneumatic bias regulator in the controller output to simulate a load change at the process input. We can do it by transferring the controller to Manual while in a steady state, stepping its output and immediately transferring to Auto.

Page 1 of 4 « Prev 1 | 2 | 3 | 4 View on one page
Share Print Reprints Permissions

What are your comments?

Join the discussion today. Login Here.

Comments

No one has commented on this page yet.

RSS feed for comments on this page | RSS feed for all comments