Intrinsic Safety (IS) makes it possible to perform live maintenance at any point in the control loop because, by its nature, it always keeps the amount of available energy on the wire pair below the ignition point for the gases/environment in which it's installed. There are two aspects to determining the hazardous area requirements for an installation: area classification (the type of gas present and the likelihood of its being present) and the temperature classification (maximum surface temperature of the device or apparatus).
ADVERTISEMENT
The following figure shows how area classifications are determined for North America using the class-and-division principle. The division is based on the likelihood of a specific type of gas being present at any point in time. As a rule of thumb, Division 2 assumes the potentially explosive gas is present one hour/year, while Division 0 assumes the gas is always present (Figure 1).
The second aspect of hazardous area control is the temperature rating. Figure 2 shows how the type of gas present determines the required "T-rating."
Fortunately, the majority of the hydrocarbon industry only needs to meet the T1 or T2 temperature limitations for the majority of its facilities, and this is often why the T-rating is overlooked when specifying and purchasing instruments. When we think about temperatures, we tend to be more concerned with the ambient temperature range in which the device can continue to operate.
Intrinsic safety is entity-based, meaning all the components need to be considered as a single entity. The devices in the loop also need to be treated as "simple apparatus" as defined in ISA–60079-11 (12.02.01)–2009 "Explosive Atmospheres—Part 11: Equipment Protection by Intrinsic Safety," which is summarized below:
Simple apparatus are defined as those devices in the following three categories:
In addition to the above, the following (taken from the ISA standard) also applies to simple apparatus installations:
Because with entity systems, you need to understand interaction between each component on a loop, I/O card, barrier or field device, the entity concept works well for loops with one I/O card and one field device. However, if you have multiple devices on a wire pair, as with fieldbus systems, the number of combinations that need to be verified quickly grows exponentially. This is one of the reasons most process fieldbus systems use FISCO as described in the June 2010 issue of Control (www.controlglobal.com/articles/2010/FISCO1006.html).
Furthermore, intrinsically safe (IS) circuits need to be kept separate from non-IS circuits with the following minimum requirements:
The final critical element in any IS circuit is the important issue of what to do with any "extra"energy that might result in the event of a fault in the loop, such as a short circuit. Normally the answer is to run this current to ground or earth. Figure 3 shows a typical control room/interface room earthing/ground scheme.