Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation
ControlGlobal.com
05/18/2010
By Dr. Jun-koo Kang, Yaskawa Electric America
Adjustable speed AC drives are mainly made up of two power sections, i.e., a rectifier section and an inverter section. The AC source voltage is converted into a DC voltage by the rectifier circuit, and then the DC voltage is converted again into a PWM controlled variable voltage AC output by the inverter circuit. The six-diode bridge rectifier is most widely used as an AC-to-DC converter. This diode rectifier has a nonlinear (i.e. non-sinusoidal) load characteristic causing harmonic currents flow into the power source and results in line voltage distortion. Excessive harmonics in a power source raise many practical problems such as;
- The rms current increase and input power factor reduction
- Overheating of grid-connected motors, cables, transformers, and other distribution equipment
- Resonating and harmonic heating of the power factor correction capacitors
- Nuisance tripping of the thermal circuit breakers
- Malfunction of PLCs, computers, and other harmonics sensitive equipment.
The Yaskawa E7,F7,G7, and P7-series drives above 30HP have a built-in DC link choke as a standard easily mitigating input current harmonics. In case of six-diode bridge rectifier, the input current Total Harmonic Distortion (THD) is approximately 40% at a full load condition. The harmonic currents can be further reduced to about 30% with the addition of input AC reactors in combination with a DC link choke. For further harmonics reduction, multipulse rectifier topologies are good practical solutions, which reduce input current harmonics to levels below 10%. This paper introduces general features and advantages of Yaskawa's multi-pulse solutions that include 12-pulse and 18-pulse rectifier topologies.
More News:
-
05/15/2013
Alarm Mobility Increases Hydro Plant Reliability
integrating the TopView Alarm Notification Software with the SCADA System, Operators Are Now Able to Receive Alarm Messages in Real-Time on Their Cell Phones and Can Acknowledge These Alarms from Anywhere
- 05/09/2013 groov gets IOS and Android apps
- 05/01/2013 Swagelok publishes comprehensive sampling systems reference book
- 05/01/2013 Krohne provides instrumentation for Chobani plant
- 04/19/2013 Attendees Learn About Suppliers' Latest Foundation Products
- 04/19/2013 Huang Buyu, Now Retired from Sinopec SEI, Is Honored
- 04/19/2013 Dave Glanzer Addresses General Assembly Attendees
- 04/19/2013 FOUNDATION Fieldbus-Certified Training Center
- 04/19/2013 FOUNDATION Fieldbus Technology Helps Power Company Save
- 04/19/2013 Foundation for Remote Operations Management (ROM) Provides an Extended Information Architecture
- All news »
Sponsored Links
Control Digital Edition
Access the entire print issue on-line and be notified each month via e-mail when your new issue is ready for you. Subscribe today.
- Featured White Papers
Print page