Reader Feedback: Lambda Tuning: Use It or Lose It?

Helpful If Readers Could Get Better Information Than What's Listed in The Last "Control Update" Under: "Cascade Control Recommendation Tips" in Greg McMillan's "Control Talk" Blog

By Sigifredo Nino

It would be very useful if the readers could be better informed than the recommendation listed in the last "Control Update" under the title: "Cascade Control Recommendation Tips" in Greg McMillan's "Control Talk" blog.  Number 8 is "Do not use setpoint filters on lower loops. Use lambda tuning for coordination of flow loops (e.g., maintaining stoichiometry for inline blending and reaction control). Set the lambda (closed-loop time constant) of each loop to match the lambda of the slowest loop.' I find it very saddening that even after someone of the stature of Greg Shinskey gets his paper, "A Case against Lambda Tuning" (http://bit.ly/1m8qygm) published in your May 2012 magazine, and that over the years, several people from industry and academy, including one of the inventors of the IMC tuning, have acknowledged the inherent deficiency of the method to cope with the most frequent dynamic behavior found in process control, your magazine keeps promoting it through this type of recommendation.

Sigifredo Nino
Summa Control Solutions

Greg McMillan replies:

Let me first say I think Greg Shinskey has provided an understanding of the effect of process and equipment design on dynamics and PID control in his books that goes far beyond what anyone else has done.

I shared Shinskey's concern about lambda tuning for over a decade. The major concern centered on a reset time that was much larger than what is needed to return to setpoint after a load disturbance to self-regulating processes with a large time constant to dead time ratio. Many of these loops are very important in that they involve concentration, pH and temperature control of large, continuous, liquid unit operations such as distillation, neutralization and reaction. A second concern was the lack of derivative action for these processes.

I realized about two years ago that if I switch from lambda tuning rules for self-regulating processes to lambda tuning rules for integrating processes with derivative action, when the time constant to dead time ratio became greater than three and I used a lambda equal to half the dead time, the problem that Shinskey raised about the recovery from load disturbances largely goes away. In fact, the tuning settings converge to those of the Ziegler-Nichols reaction curve method and many other tuning methods based on minimizing the peak and integrated error for disturbances at the process input (load disturbances).
In the lambda integrating process tuning rules, the lambda becomes the arrest time for the load response, which is more appropriate for these processes. In the lambda tuning rules for self-regulating processes, lambda was the closed-loop time constant for a setpoint response. The rate time is set equal to the secondary time constant in a second order plus dead time approximation. If the secondary time constant is not identified, I use one-half of the dead time as an inferred secondary time constant.

To provide more robustness and less tendency for the loop to oscillate, I have since used the rule of thumb to switch from lambda tuning rules for self-regulating processes to lambda tuning rules for integrating processes when the time constant to dead time ratio is greater than four, and use a lambda equal to the dead time. To deal with unknown nonlinearities that cannot be corrected by adaptive tuning and for interaction that cannot be corrected by decoupling, and to reduce resonance from disturbance oscillations with a period close to the ultimate period of the loop, I have increased lambda to be three dead times.

For more of this discussion, go to the comments section on article "Cascade Control Recommendation Tips."

More from this voice

Title

Reader Feedback: Process Automation, Control Valves vs. VFDs and More

Readers Agree, Disagree and Respond to Some of Our Latest Articles. See What They Have to Say

05/02/2011

Reader Feedback: Process Safety

Sometimes Even the Best Maintenance Practices Fail to Manage to Keep Some of These Plants Safe

03/04/2013

Reader Feedback: Replacing a Field Device

Is the 3 a.m., Sunday Morning Replacement the Killer App?

03/05/2014

Reader Feedback: Simulation Speed-Up a Good Thing

More and More, Dynamic Simulations Are Used Before Start-Up of a New Plant for Operator Training

12/17/2013

Reader Feedback: What Color Is Your Hat?

Black Hat Caters to the Hackers and Security Researchers Primarily from the IT Community, as Well as the Press

10/10/2013

Reader Feedback: When Should You Calibrate Your Industrial Devices?

A Reader Says "You Should Calibrate Your Instruments With the Frequency You Established in [Your] Plan, and Never Go Longer Than a Year"

04/07/2014

Reader Feedback: When Will There Be an App for That?

A Reader Asks Us When Will We Have an App for iPad

03/06/2013

Reader Feedback: Who's the Boss?

Google Doesn't Respect Authority. Google Search Results Are Only a Reflection of the Respect Granted by Others

05/01/2013

Reader Feedback: Why Is Alarm Management Such a Problem?

What's the Cost of Best Practice Alarm Management?

01/14/2014

Reader Feedback: Wired vs. Wireless

A Reader Tell Us About Powerline Communication

03/05/2013

Readers Respond to Cybersecurity and Temperature Measurement Compensation

Readers Agree With Our Cybersecurity Coverage and Ask Why the Methods of Compensation Were Not Addressed by Our Industry Experts

07/05/2011

Really? A Political Diatribe?

Reader Disagrees with Editor in Chief Walt Boyes's View on External Cyber Attacks Dangers and U.S. Cybersecurity Policies

02/06/2012

Safety First?

The Wind Power Industry Is Experiencing a Learning Curve in Safety and Accident Prevention

01/05/2012

Securing Control Systems in Cyberspace

One of Our Readers Says That Even the ISA99 Memeber Will Say It Is Hard to Quantify Security From Their Security Access Level (SAL) Work

10/02/2012

STEM: Competent People Reply

Lets Help Our STEM Students While They're Still Students

06/04/2012

Summer and Stuxnet

Talking Plant Cybersecurity in the Light of Stuxnet. With No Certifications for Control System Cybersecurity, Anyone Can Be an Expert. Who Does an End User Believe?

08/02/2011

Taking on Industrial Control Security Issues

What's It Going to Take Before We Start Getting Real about Industrial Control Security Issues

04/03/2012

Technology: Keep the Print

Don't ever Kill the Magazine

08/27/2012

Thanks for the Thought

Seeing Things in a Different Way. It Takes a Little More Than Just Turning On the Faucet to Get a Drink

06/05/2012

The Case Against Lambda Tuning

Understand the Framework of Using Internal Model-Based Control (IMC) to Come Up With PID Parameters

07/31/2012