Measuring Viscosity With Coriolis Flowmeters

It Can Be Deduced From the Excitation Coil Current

By Dan Hebert

The Earth rotates, so any movement in the Northern hemisphere is diverted to the right and any movement in the Southern hemisphere is bent to the left. This apparent bending force is known as the Coriolis force, and is named after the French mathematician Gustave Gaspard Coriolis (1792-1843).

Since the 1970s, instrument designers have used the principle of Coriolis force to measure mass flow and density with Coriolis flowmeters. Most of these meters also include temperature measurement and are thus true multivariable instruments.

Read Also: Coriolis for the Masses

A traditional method for measuring viscosity with mass flowmeters is to add a differential pressure (DP) meter. Viscosity is the measure of a fluid's internal or intermolecular resistance to shear stress. Certain types of fluids offer greater resistance to velocity than others. Tar or syrup cannot be poured easily and have high viscosities. Water or gasoline are "thinner" and have much lower viscosities.

A DP meter can be installed around the mass flowmeter with taps upstream and downstream. Viscosity is measured by determining the pressure drop through the mass flowmeter. The viscosity of the flowing medium is directly proportional to the ratio of pressure drop and volumetric flow rate. This calculation of viscosity is based on the Hagen-Poiseuille equation and is expressed as absolute viscosity.

Viscosity measurements with Coriolis and DP have some limitations in addition to the obvious cost of two separate meters. The Hagen-Poiseuille equation is only valid for laminar flows with a Reynolds number less than 2,000. This often forces the use of larger and more expensive meters to minimize flow velocity. The flow profile must be uniform throughout the DP measurement section of the process, and the Hagen-Poiseuille equation is also only theoretically valid for Newtonian fluids.

These limitations have spurred research into methods of measuring viscosity directly with a Coriolis meter. Research at Endress+Hauser has resulted in the recent introduction of direct viscosity measurement in the company's Promass 83 I line.

Coriolis flowmeters measure the rotational force exerted by fluids flowing through an oscillating measurement tube. Measurement of these forces is used to calculate mass flow and density. Endress+Hauser uses the torsional movement of the single straight measuring tube to additionally measure the viscosity of the fluid.

Read Also: How Do Coriolis Flowmeters Work?

Promass Coriolis flowmeters use a patented torsion mode balance system for optimum balance and isolation from external influences. A pendulum is attached to the middle of the oscillating measuring tube to provide a balancing force. This pendulum oscillates counterphase to the tube, thus compensating for the momentum of the measuring tube.

Due to the rotational motion of the tube, the fluid is forced to a rotational motion. Depending on the fluid's viscosity, different velocity profiles of the fluid are generated. The gradient of the velocity profile induces shear forces in the fluid, which dampen the oscillation of the measuring tube and can be measured via the excitation current necessary to maintain tube oscillation. The excitation current can then be used to calculate the viscosity of the fluid.

The accuracy of viscosity measured with this patented method depends on whether the fluid is Newtonian or non-Newtonian. The viscosity of Newtonian fluids is independent of shear rate. Water is a Newtonian fluid, so its viscosity is not affected by shear rate. Stated differently, water will pour out of a container at the same rate if the water is still or if the water is being stirred.

The viscosity of Newtonian fluids can be measured with a high rate of repeatability and reasonable accuracy. "The total accuracy equals ±5% of reading and the repeatability is 0.5% of reading," according to Stefan Grotzer, flow product manager, Endress+Hauser.

If the viscosity changes with shear rate, the fluid is non-Newtonian. The effect of shear rate depends on the type of fluid--some non-Newtonian fluids have a reduced viscosity when shear rate is high, some the opposite effect (increased viscosity with higher shear rate). Ketchup is a good example of the former: it is usually necessary to shake the ketchup bottle to induce flow. This shaking or shearing reduces the ketchup's viscosity and promotes flow.

The accuracy of viscosity measurements for non-Newtonian fluids is adversely affected by shear rates generated by the Coriolis meter and by other elements. However, Coriolis meters can measure the viscosity of non-Newtonian fluids with good repeatability.

Coriolis meter viscosity measurement of non-Newtonian fluids is typically used where the target is a repeatable measurement and where continuous correlation to a lab measurement is not required. A change in viscosity can be an indication of a process problem, or can indicate the product is outside the acceptable limits of viscosity.

More from this voice

Title

Measuring Viscosity With Coriolis Flowmeters

It Can Be Deduced From the Excitation Coil Current

05/14/2003

Technically speaking: Will standards mesh?

Reliability, scalability and mobility are the trump cards of wireless mesh networks and should result in triumph over other wireless topologies, according to Senior Technical Editor Dan Hebert, PE.

10/24/2004

Process controllers don't do windows

Embedded operating systems dominate the process control market, but this soon could change according to Senior Technical Editor Dan Hebert in his monthly Technically Speaking column for CONTROL.

02/22/2005

Make your automation processes better

There is no lack of technologies available that can improve your automation systems. The trick is to find, evaluate, and implement them without spending an inordinate amount of time, or taking on too much risk.

05/20/2005

An alarming situation

Alarm systems of one type or another always have been part of industrial machine, robot, and skid control systems, but CONTROL Senior Technical Editor Dan Hebert, PE, notes that there's more to alarm technology than meets the eye ... or ear for that matter.

06/05/2005

Applied control theory moves out

Industry group gets automation industry support from companies that believe the partnership between industry and academia is most beneficial when theory moves out of the classroom and into the plant.

06/20/2005

Do you need a single-source middleware solution?

As integrated middleware solutions vie with best-of-breed products, Senior Tech Editor Dan Hebert wonders if there will ever be a true integrated solution that covers the entire middleware space?

07/21/2005

Use RFID to improve your automation systems

Senior Technical Editor Dan Hebert, PE, addresses RFID technology and explains how RFID systems are being lnked to process automation systems to deliver process improvements.

08/22/2005

Fiber optic sensors on the horizon

The spread of fiber optic sensor technology from the laboratory into everyday use has barely begun. It's slashed the cost of communications, and may be poised to do the same for sensing applications.

09/27/2005

Into the mesh

Senior Tech Editor Dan Hebert, PE, identifies the leading candidates for best system architecture supremacy in the wireless arena and believes software algorithms will be key for high bandwidth mesh networks.

10/19/2005

Is advanced control ready for Prime Time?

Fuzzy logic can minimize false alerts without compromising detection and notification of actual events, but there is always a tradeoff between sensitivity and increasing likelihood of false notification.

11/10/2005

Old flywheel technology finds new uses

Read how high-tech flywheels can be used in place of batteries in process plant UPSs when backup power is needed during short-term disturbances and to ride through from utility to generator power.

12/21/2005

Web mash-ups: 1+1=3

CONTROL Senior Tech Editor Dan Hebert, PE, takes an in-depth look at a new web technology that will affect how you'll use the Internet, and how this latest trend could be applied to automation.

01/16/2006

Standards bring order to chaos

Implementation of the New Sampling/Sensor Initiative (NeSSI) standards will simplify sample system design, installation and operation, fundamentally changing and improving the way we do process analysis.

02/10/2006

HMI software is disappearing

Senior Tech Editor Rich Merritt takes a look at the HMI marketplace and finds today's software packages are getting better and cheaper, but are increasingly disappearing into control system vendors' portfolios.

02/13/2006

The right tool for the job

The next horizon for portable HMI applications may be the cell phone, which is cheap, ubiquitous, and produced in larger annual quantities than any consumer electronics device in history.

03/20/2006

Data logger size matters

New requirements and regulations are constantly being foisted on you and your plant, and many of these requirements necessitate acquisition and recording of data. Compact data loggers offer a solution.

04/17/2006

PC-based control infiltrates process plants

As PC-based control becomes more widespread in process plants, often via purchased machines and process skids, companies are finding it's a short step to implementing it for control over critical processes.

05/15/2006

Who should do your next project?

Senior Tech Editor Dan Hebert, PE, takes a look at ways you can make an automation contractor selection based on project size, scope, and support requirements in this installment of Technically Speaking.

06/12/2006

Who should do your next project? Part 2

In part two of this two-part series, Senior Tech Editor Dan Hebert, PE, takes a look at how your company’s own internal capabilities and characteristics can affect automation contractor selection.

07/14/2006