Voices: Hebert

Measuring Viscosity With Coriolis Flowmeters

It Can Be Deduced From the Excitation Coil Current

By Dan Hebert

The Earth rotates, so any movement in the Northern hemisphere is diverted to the right and any movement in the Southern hemisphere is bent to the left. This apparent bending force is known as the Coriolis force, and is named after the French mathematician Gustave Gaspard Coriolis (1792-1843).

Since the 1970s, instrument designers have used the principle of Coriolis force to measure mass flow and density with Coriolis flowmeters. Most of these meters also include temperature measurement and are thus true multivariable instruments.

Read Also: Coriolis for the Masses

A traditional method for measuring viscosity with mass flowmeters is to add a differential pressure (DP) meter. Viscosity is the measure of a fluid's internal or intermolecular resistance to shear stress. Certain types of fluids offer greater resistance to velocity than others. Tar or syrup cannot be poured easily and have high viscosities. Water or gasoline are "thinner" and have much lower viscosities.

A DP meter can be installed around the mass flowmeter with taps upstream and downstream. Viscosity is measured by determining the pressure drop through the mass flowmeter. The viscosity of the flowing medium is directly proportional to the ratio of pressure drop and volumetric flow rate. This calculation of viscosity is based on the Hagen-Poiseuille equation and is expressed as absolute viscosity.

Viscosity measurements with Coriolis and DP have some limitations in addition to the obvious cost of two separate meters. The Hagen-Poiseuille equation is only valid for laminar flows with a Reynolds number less than 2,000. This often forces the use of larger and more expensive meters to minimize flow velocity. The flow profile must be uniform throughout the DP measurement section of the process, and the Hagen-Poiseuille equation is also only theoretically valid for Newtonian fluids.

These limitations have spurred research into methods of measuring viscosity directly with a Coriolis meter. Research at Endress+Hauser has resulted in the recent introduction of direct viscosity measurement in the company's Promass 83 I line.

Coriolis flowmeters measure the rotational force exerted by fluids flowing through an oscillating measurement tube. Measurement of these forces is used to calculate mass flow and density. Endress+Hauser uses the torsional movement of the single straight measuring tube to additionally measure the viscosity of the fluid.

Read Also: How Do Coriolis Flowmeters Work?

Promass Coriolis flowmeters use a patented torsion mode balance system for optimum balance and isolation from external influences. A pendulum is attached to the middle of the oscillating measuring tube to provide a balancing force. This pendulum oscillates counterphase to the tube, thus compensating for the momentum of the measuring tube.

Due to the rotational motion of the tube, the fluid is forced to a rotational motion. Depending on the fluid's viscosity, different velocity profiles of the fluid are generated. The gradient of the velocity profile induces shear forces in the fluid, which dampen the oscillation of the measuring tube and can be measured via the excitation current necessary to maintain tube oscillation. The excitation current can then be used to calculate the viscosity of the fluid.

The accuracy of viscosity measured with this patented method depends on whether the fluid is Newtonian or non-Newtonian. The viscosity of Newtonian fluids is independent of shear rate. Water is a Newtonian fluid, so its viscosity is not affected by shear rate. Stated differently, water will pour out of a container at the same rate if the water is still or if the water is being stirred.

The viscosity of Newtonian fluids can be measured with a high rate of repeatability and reasonable accuracy. "The total accuracy equals ±5% of reading and the repeatability is 0.5% of reading," according to Stefan Grotzer, flow product manager, Endress+Hauser.

If the viscosity changes with shear rate, the fluid is non-Newtonian. The effect of shear rate depends on the type of fluid--some non-Newtonian fluids have a reduced viscosity when shear rate is high, some the opposite effect (increased viscosity with higher shear rate). Ketchup is a good example of the former: it is usually necessary to shake the ketchup bottle to induce flow. This shaking or shearing reduces the ketchup's viscosity and promotes flow.

The accuracy of viscosity measurements for non-Newtonian fluids is adversely affected by shear rates generated by the Coriolis meter and by other elements. However, Coriolis meters can measure the viscosity of non-Newtonian fluids with good repeatability.

Coriolis meter viscosity measurement of non-Newtonian fluids is typically used where the target is a repeatable measurement and where continuous correlation to a lab measurement is not required. A change in viscosity can be an indication of a process problem, or can indicate the product is outside the acceptable limits of viscosity.

More from this voice

Title

Stop wasting money on backup power

The most prudent and cost-effective strategy for dealing with power-quality events is to protect against relatively frequent, short-term voltage sags as opposed to much rarer power outages.

08/10/2006

Welcome to the Bus Wars, Part Tres

You may not be aware, but a new bus war is being waged in your plant — the battle of the motion networks. Senior Tech Editor Dan Hebert, PE, provides analysis and commentary on the newest battle over fieldbus.

09/01/2006

User-friendly advanced control

Senior Tech Editor Dan Hebert, PE, looks at the latest advances in simulation and modeling technologies for improved loop control, including new software packages and embedded APC systems.

10/26/2006

Analyzers not ready for prime time

It is easy to see why the analyzer market doesn’t work for end users, but it is harder to find a solution. Clues can be found, however, in one small part of the analyzer market that is improving rapidly.

11/02/2006

AutomationXchange event report

While basic plant-floor automation is no longer a mystery, advanced control often is, making techniques for solving difficult process control problems of high interest to end users and service providers.

12/14/2006

Alarm management improves plant operations

Alarm management is a hot topic, perhaps because incorrect presentation of alarms often confuses operators. This article shows how better alarm management empowers operators to improve plant performance.

01/05/2007

Digital fieldbus networks

It's not so easy to deploy digital fieldbus networks in existing process plants. Working to upgrade from discrete and analog connections to digital fieldbus networks presents a host of options and challenges.

02/01/2007

Data access from everywhere

Limitations have kept mobile data access on the tradeshow floor and out of most process plants, but things are changing for the better because of a number of hardware and software tools that are making it practical.

03/08/2007

Why calibration measurement software?

Field calibration is faster and more accurate with digital calibrators and a CMS, but there’s a catch. Senior Tech Editor Dan Hebert, PE, reports on the state of the art in calibration systems for the operator.

04/06/2007

The skinny on PC-based control systems

In this column, Senior Tech Editor Dan Hebert, PE, takes a look at why a process skid manufacturer thinks PC-based control makes sense for its—and other—process applications.

05/07/2007

Fieldbus in hazardous areas

Digital fieldbus networks have created new options for installing devices in hazardous areas by simplifying implementation of IS systems and avoiding explosion-proof enclosure conduit systems.

06/08/2007

Mission Control

Custom-built command-and-control centers are an expensive option, but they provide concrete benefits.

07/15/2007

A Too-Smart Solution?

The benefits of installing smart metering systems in the plight of utilities are clear, but implementation is complex.

08/01/2007

Sparky, Sparky, Zap!

Neither spark-gap devices nor silicon avalanche diodes are a good fit for protecting process-plant electronics.

08/30/2007

How Good is OPC-UA, Really?

Even after consulting the experts, it’s hard to tell if OPC-UA will live up to its promise.

10/02/2007

Mission Control

Every process plant has a control room with numerous display devices. Some old plants still have large custom-built mimic panels, while newer plants have two main choices for display systems.

11/05/2007

Open Control Programming at Last?

Vendors were able to co-opt IEC61131, and some are wary of the same danger with respect to the new IEC61499.

11/07/2007

More Fiber in Your Network Diet

It is extremely difficult to eavesdrop on fiber-optic connections, guaranteeing a high degree of security.

12/10/2007

PACs for Communications and Data Handling

Process Control Tasks Performed by the PAC Include Closed-Loop PID Control of a Set of Heaters That Maintain the Sampling Ports at Constant Temperatures

01/04/2008

Calibrate This—Electronically

Moving From a Paper-Based System to an Automated One Can Bring a 15% to 25% Improvement in Efficiency

02/05/2008