Voices: Lipták

"Herding" Control and LPG Problems

A Reader Asks Us if "Herding Control" Is a Theoretical Concept, or a System that Our Very Own Bela Liptak Designed. Also, What Is the Suitability of Using a Differential Pressure Cell Pressure Transmitter.

By Bela Liptak

Q: In your articles, you have discussed "herding control" as a valuable tool in multivariable safety and optimization applications. Is that strategy a theoretical concept, or did you actually design such systems? Have you used herding control in actual applications?

H. Crowney
HCrowney@aol.com

A: Yes, I did use the "Puli" algorithm to optimize several combustion processes, keeping a number of controlled variables (CO, HC, excess O2, temperature, opacity) within safe limits inside a "control envelope." I also used it in a computer chip manufacturing application, and once in a building optimization one.

My best known application was the optimization of the IBM headquarters building at 590 Madison Avenue in New York City, where I optimized the energy consumption by "herding" the heat generated in the interior offices (offices without windows that require cooling even in the winter) to the perimeter offices that have windows, and, therefore, require heating in the winter.

Bela Liptak
liptakbela@aol.com

Q: I have two questions. We have an existing liquefied petroleum gas (LPG) spherical tank. On it, there is an external-cage, low-level switch. Some modifications are going on, and we have to install an additional level transmitter in parallel with the existing level switch.

I'm asking about the suitability of using a differential pressure cell pressure transmitter and what precautions should be considered to get accurate readings? Shall we use a diaphragm seal or impulse lines filled with a special liquid?

What other choice can we use instead of using a differential pressure cell pressure transmitter?

My second question is this: We have existing LPG spherical tanks. We are going to implement some modifications to the inlet/outlet pipeline on these LPG tanks. One shutdown valve will be installed in the inlet line and one in the outlet line. The client asked us to use (if applicable) shutdown valves with self-detecting pressure drop to close this valve in case of line rupture.

According to my experience, we have to install differential pressure transmitters across the shutdown valve to detect the pressure drop in case of line rupture, but the use of differential pressure measurement requires too much straight line upstream and downstream of the shutdown valves, and in this old plant we do not have it. The client asked us to make survey in the market to find a suitable solution for this problem.

I'm asking about a shutdown valve with the capability to self-detect the pressure drop/loss inside the fluid line (LPG). Is there a pneumatically actuated shutdown valve with self-detecting pressure drop? If yes, what is the vendor name and contacts? Is it proved in the LPG application? What are some of the other suitable solutions for this requirement?

l Ragab Abdel Fattah
ragab.abdelfattah@tecnomareegypt.com
Fattah

A: To answer your first question, from the point of view of reliability and availability, my preference is to use a radar gauge. However this would require a large nozzle on the top of the tank and would cost more.

If you decide to use a differential pressure transmitter, you have the following options:

  1. Fill the low pressure connection with a glycol to seal it.
  2. Use chemical seals with capillary connections to the differential pressure cell.
  3. Check with Emerson on the applicability of their remote sensor (3051S ERS). I have not tried it so far.

However it might overcome some of the issues with above options.

In the matter of your second question, since you are installing a differential pressure transmitter for determining the pressure difference, but are not measuring flow, there is no requirement for a straight pipe run. The only thing you should do is study where to install the low-pressure tapping and what setting to select to alarm a leak. Your hydraulic guy can advise this.

Harvindar Gambhir
Harvindar.S.Gambhir@ril.com

A: I suggest using a magnetostrictive level sensor, such as manufactured by MTS. It would have a float that floats on the liquid phase of the LPG.  The float incorporates a set of magnets, and the sensor detects the position of the magnets within about 0.0005 inch.  [Note from Béla Lipták: the position of the magnets might be detected accurately, although not that accurately, but the relationship between the magnets position and the level is much less accurate, because that is also a function of the vapor and liquid densities, which vary with temperature and pressure.]

Dave Nyce
DNTHX1138@aol.com

A: Differential pressure measurement is proportional to level, if the densities of both the liquid phases are considered: (density liquid – density vapor). Otherwise, any condensation in the nominally "dry" leg will give a zero error.

Whether LPG "heavies" can condense depends on the ambient temperature swing. A glycol filled "dry" leg is a good solution. I am less enamored of using capillary systems, which can be sensitive to sunlight exposure (try to keep them on the shady side of the tank). Rosemount's system of a HART-coupled LP sensor may be worth exploring.

The magnetostrictive float transmitters can be a good solution, but can be more difficult to install. Note that these have zero error if (liquid density – vapor density) varies significantly, to the point where the float just sinks. The zero error can be as much as 60% of the float length.

Guided-wave radar will work on LPG if selected properly and it's economical, but it really works best inside the vessel, rather than in an external chamber where the LPG may boil due to solar exposure. Thermal insulation can be desirable on external chamber devices of any sort if solar radiation is significant.

Ian H.Gibson
gibs0108@optusnet.com.au

A: In answer to your second question, do this by operating a pneumatic control valve on the basis of pressure drop across it; a lower-maintenance and less expensive solution is to use check valves.   

On the inlet line to the vessel, you need to install a regular check valve "in reverse," meaning that it is fully open when the flow direction is into the tank, but closes as soon as the flow direction reverses. On the discharge line from the tank, you should use an excess flow check valve (EFCV).

The EFCV consists of a plug, a seat and a spring, all housed or supported in a cylindrical tube. The valve connections can be screwed or flanged as shown in Figure 1.

Under normal operating conditions, the force generated by the flowing process fluid is directed against the valve head and attempts to close it, but the spring is stronger and keeps the valve open. If the flow suddenly increases to an excessive rate, the force against the plug and the differential pressure across it overcomes the spring force, and the valve closes. The EFCV does not require up- and downstream straight runs as the velocity profile across it does not matter.

Inside the EFCV, there are one or more bleed ports around the plug, so that after the valve closed, the bleed can equalize the pressures up- and downstream of the plug, so that it can reopen, if the pressures equalize. However, if a pipe break occurs, the differential pressure across the valve will remain constant (the difference between the pressure on the tank and the atmosphere downstream), and the valve will stay closed until the pipe is repaired. It should be remembered that because of the required seepage through these valves (which provides their equalizing feature) they will not give tight shutoff.

Béla Lipták
liptakbela@aol.com

A: You can contact Festo Pneumatics, which can provide the following mechanism/pneumatic hook up: a 3/2 N/O (read 3-way, 2-position, normally open) valve, pneumatic operated by loss of pressure, spring-returned, normal position. The required air supply is 6 bar to above the 3/2 N/O valve, while its outlet port above the 3/2 N/O valve connects to your automatic pneumatic shut-off valve. The port that triggers this valve connects to your rupture line for sensing loss of pneumatic pressure.

To increase safety, you can provide redundancy for logic validation on line rupture.

I found such systems on the Internet, by using the key words: "Shutdown Valves, LPG."  Your problem is interesting. I am not sure if any of these valves have gotten TÜV approval for emergency shutdown based on the SIL of your plant.

Gerald Liu
gerald.liu@shaw.ca

A: Do not worry about the straight line segment. That is a requirement for precision flow measurement, but not for your safety systems application. In fact, you cannot use the d/P information for accurate flow measurement since your valve is not an orifice with known diameter. So just install a conventional low-accuracy (if that is less expensive) D/P transmitter across the shutdown valves. The reading at normal times will be zero flow, and some positive reading in case of valve failure to completely shut off. However, I do not understand how a D/P across the valve can detect line rupture without some type of piping diagram.

Richard H. Caro
RCaro@CMC.us

More from this voice

Title

Pumping Station Optimization, Part 3

The Optimization of Pumping Stations and Liquid Distribution Systems Can Save 25 Percent or More Energy

03/04/2010

Rangeability of Equal Percentage Control Valves

A Reader Turn to Our Experts For Advice on Installing a Control Valve. See What Our Experts Had to Say

09/12/2013

Real-Time PIG Data Transmission?

How Can We Improve the Safety of the Pipelining Industry? See What Our Experts Say

11/12/2012

Relief Valve Blowdown Rings; D/P and Straight Runs

Readers Ask: When It Comes to Safety Relief Valves, What Is Best? Using Two Blowdown Rings or Ones? and Can a Transmitter Be Installed Above Pipe Taps?

05/07/2013

Renewable Energy Processes, Part 2

The Control System Must Be able to Detect the Loss of the Grid and Respond by Isolating Itself from the Grid or by Tripping Offline

07/02/2010

Scraping of the Bottom of the Barrel -- Fracking

Proponents Believe Fracking Gas Could Meet U.S. Energy Needs for a Century. Opponents Say the NG Supply Will Be Exhausted in Just a Few Decades

12/30/2011

Scraping the Bottom of the Barrel-Part 3

Liptak Discusses Pipelining Safety and How Automation Processes Can Prevent Pipelining Accidents

03/02/2012

Sealing an Oil Well; Orifice Sizing--OSO versus AGA

Can Someone Explain BP's Sealing Process to Temporary Seal the Oil Well from the BP Oil Spill in the Mexican Gulf? And, What Is the Difference Between the Orifice Calculations Described by AGA 3 and ISO 5167?

04/10/2013

Software for Renewable Energy Processes - 4

Talking About Software Needs for Control and Optimization of Solar Energy Storage and Transportation Systems

10/05/2011

Software for Renewable Energy Processes - 4

Solar Is the Fastest Growing Power-Generation Technology in the World

10/28/2010

Software for Renewable Energy Processes-5

Bela Liptak Describes the "Battery Swap"-Based Transportation and the "Energy Free" Housing He Sees for the Future

01/10/2011

The Energy Future—Process Control’s Role

Find out about the “zero energy home of the future” and the hydrogen economy. What are the potentials of process control in wind, ocean wave, and geothermal energy systems.

07/12/2007

The Fukushima Nuclear Accident - Part 1

Béla Lipták Talks About the Safety Processes Used at the Fukushima Plant

04/15/2011

The Future of Nuclear Energy

If Global Carbon Emissions Were Cut by 15% by 2050 by the Increased Use of Nuclear Power, 1,070 Plants Would Need to Be Built at a Cost of $5 Trillion.

03/02/2009

The Global Energy Future – Part 5

Covering 10 million American homes with solar roofs would trigger the biggest economic expansion of the decade.

08/31/2007

The Incredible Fiber-Optic Flowmeter

Online, Real-Time Multiphase Measurements Improve Safety of Oil and Gas Production

05/02/2014

The Third Industrial Revolution

The Transition to a Solar/Hydrogen Economy Will Trigger an Economic Boom Unseen Since the Marshall Plan.

03/07/2008

The fuel cell: A new process to control

The fuel cell is like a battery, except that it never needs recharging because the heat and electricity produced by it are made from the inexhaustible and clean sources of water and air.

09/20/2002

The global energy future – Part 3

Control's own Béla Lipták continues his series on the future of global energy, stating that in order to obtain maximum energy recovery, the various solar collectors described all need to track the sun.

05/07/2007

The next generation of smarter valves

In the next decade, much improvement and change is expected in the design of smart and self-diagnosing control valves, with potential advantages outweighing the required investment of time and money.

05/10/2005