Aurora is real and has caused damage

Dec. 4, 2016

In preparation for a new book, I was able to find information about an actual Aurora event. The event affected a non-utility facility (no generator involved) where it experienced multiple Aurora events over a multi-day span resulting in damage to motors.

I have written frequently about the Aurora vulnerability. In preparation for a new book, I was able to find information about an actual Aurora event. The event affected a non-utility facility (no generator involved) where it experienced multiple Aurora events over a multi-day span. The events originated from the utility which was outside the facility’s control (Aurora can affect nuclear plants, refineries, water facilities, pipelines, hospitals, data centers, and other critical facilities who “are at the mercy” of the utility for Aurora mitigation). The Aurora events damaged motors with one of the motors out of operation for weeks. If the motors would have been large industrial motors such as those used in power plants, refineries, mining, etc., the motors could have taken many months to repair or replace. The controller logs showed no breaker operation though the mechanical counter showed breaker operation. (This is similar to what occurred with the March 2007 INL test. The SCADA operator saw no impact until the generator coupling broke and the generator was isolated from the grid despite the fact the generator was being physically damaged without being seen. The lack of adequate forensics can impact predictive maintenance programs and confidence in remaining life estimates for critical equipment.). Finally, existing protection failed to prevent the damage. (The 2007 INL generator test, a small scale motor test at INL, and a small scale DOD Aurora test facility have all validated that existing relay protection will not prevent an Aurora event from occurring with its potential resulting damage.) This is the gap in protection of the electric grid affecting all electric substations independent of protective relay vendor. Additionally, I am aware of at least one international facility with significant damage that appears to be Aurora-related.

The demonstration of hacking a protective relay used for Aurora mitigation at the October 2016 ICS Cyber Security Conference showed how an Aurora mitigation device could be used as the Aurora initiation device www.controlglobal.com/unfettered. The 2015 Ukrainian cyber attack and the hacking demonstration should be a wake-up call to address the Aurora vulnerability.

Joe Weiss

Sponsored Recommendations

2024 Industry Trends | Oil & Gas

We sit down with our Industry Marketing Manager, Mark Thomas to find out what is trending in Oil & Gas in 2024. Not only that, but we discuss how Endress+Hau...

Level Measurement in Water and Waste Water Lift Stations

Condensation, build up, obstructions and silt can cause difficulties in making reliable level measurements in lift station wet wells. New trends in low cost radar units solve ...

Temperature Transmitters | The Perfect Fit for Your Measuring Point

Our video introduces you to the three most important selection criteria to help you choose the right temperature transmitter for your application. We also ta...

2024 Industry Trends | Gas & LNG

We sit down with our Industry Marketing Manager, Cesar Martinez, to find out what is trending in Gas & LNG in 2024. Not only that, but we discuss how Endress...