All in all, it was a good problem to have.
Frontierâs El Dorado refinery in Kansas was setting production records even as plans to add capacity kicked into gear. The problem was that the current rack room, filled with 1980s-era TDC 2000 I/O and controllers, had to be upgraded and relocated to make room for a new vacuum tower.
Given recent demandâand margins!âin the refining industry, shutting down the crude unit was unacceptable, and the migration team had to find a way to seamlessly transfer the control infrastructure to the new architecture, with nary a glitch in ongoing operations.Â
Here in Phoenix at the annual gathering of the Honeywell User Group Americas, Leland Borgett, Jeff Strecker and Tom Clark took the stage to explain how their five-person team successfully performed their âcovert cut-over,â so named for its minimal impact on ongoing operations. Their appropriately labeled T-shirts even tied into the conference theme, with âI create the solutionâ, âI implement the solutionâ, and âI maintain the solutionâ, appropriately emblazoned on each of their chests.
After reviewing a brief history of technology cut-overs experienced at the plantâfrom pneumatics and electronics to distributed control, Borgett explained that this was their first DCS to DCS cut-over. Traditionally, cut-over had involving bypassing the valve in question and returning it to service as quickly as possible so as not upset the process. This approach is difficult and time-consuming at best, he said, and this time around the team found that some of the valves didnât even have bypasses installed. Further, while they planned to perform the cut-over at the field junction boxes, tag names on the LCN couldnât be duplicated in parallel on the new system, so some creative thinking was in clearly in order.
To overcome this issue, the team came up with a unique strategy that employed a field calibrator rigged to simulate the current output of the older control system. The calibrators output was matched to current output of the control system, and, after notifying the control room that they were taking over, it was âcut and flipâ over to calibrator control. (Can you say âcontrol in the field?â) Meanwhile, with the valve controlled from the field calibrator, the point was deleted from the older control system and reinstantiated in the new.
"We then matched the new controllerâs output to that of the calibrator,â Strecker explained, âand simultaneously closely the knife switch in the new marshalling cabinet and toggled off the field calibrator.â Control room operators were then back in controlâtransparently, from their point of view.Â
âWe moved 760 I/O points in 25 days,â Borgett said. âAll with no upsets, no overtime, no loss of production and no valves bypassed. Remarkably enough, we even set some new production records in the process.â