"Rapid variations in renewable energy output wreak havoc on grid protection systems." ABB's Alan Langworthy discussed the use of flywheel/inverter systems to effectively integrate renewable energy sources onto power grids.Windmill output can vary so rapidly because the blades are made light-weight and low-inertia so they can react to gusts within the prevailing winds. "They're designed to pump energy out of the air by taking advantage of gusts," Langworthy says. These variations are happening much too quickly to be caught by SCADA systems, which may be sampling as slowly as every 15 minutes.
Battery-energy storage systems are not well-suited to absorbing and discharging energy to stabilize these oscillations. Existing batteries are able to discharge fast enough, but absorb a charge more slowly, and this asymmetrical behavior makes it difficult to use them effectively. Plus it's really hard on them, Langworthy says, "It's essentially putting an AC current on the battery."
Langworthy's group solves the problem using flywheel-based energy storage units that introduce "synthetic inertia," and are able to absorb peaks and fill sags with a reaction time of five milliseconds, an order of magnitude faster than they occur. The inverter and flywheel units correct both real and reactive power fluctuations, controlling voltage and frequency to stabilize the grid and keep renewable units online and producing usable power.
The PowerStore flywheel/inverter units can be combined with ABB communications and control systems to fully integrate renewables. With full integration, the "Goldilocks" sweet spot can be expanded enormously, in some cases up to 100%. Langworthy described, among other examples, a diesel generator and solar microgrid for the town of Marble Bar in Australia. On sunny days, a 300-kW solar array with a 500-kW PowerStore unit can power the town with no diesel generators running—and no batteries.
Goldilocks would find that to be "just right."