Basics of Analyzer Systems Busted!

Nov. 3, 2011
You're Right. Here's the Correct Wording

I'm probably not the first one to write you about this, but in Ian Verhappen's "Basics of Analyzer Sample Systems, Part 2" in the August 2011 issue, it says, "675 psi to move a column of water up at 25-ft rack…" Six hundred and seventy-five psi would move it OK—it would move it up at 309 ft/sec; i.e, a sample of it would get up there in 81 milliseconds, including initial acceleration and friction losses. In fact, a 2-in. Schedule 40 pipe with 27-ft head pressure at the bottom of the rack would get 50 gpm up the rack. Even 675 in WC would get water up that rack at > 42 ft per second.

W. Brown, C. Eng. MIET
Katy, Texas 

Editor’s note: You’re right. You're not the only one who pointed this out. The correct wording should have been, "Remember, it takes 10.84 psig to move a column of water up a 25-foot pipe rack. Conversely, and more likely, a water stream gains 10.84 psig on its way down from the same pipe rack." We regret the error.

Sponsored Recommendations

Make Effortless HMI and PLC Modifications from Anywhere

The tiny EZminiWiFi is a godsend for the plant maintenance engineers who need to make a minor modification to the HMI program or, for that matter, the PLC program. It's very easy...

The Benefits of Using American-Made Automation Products

Discover the benefits of American-made automation products, including stable pricing, faster delivery, and innovative features tailored to real-world applications. With superior...

50 Years of Automation Innovation and What to Expect Next

Over the past 50 years, the automation technology landscape has changed dramatically, but many of the underlying industry needs remain unchanged. To learn more about what’s changed...

Manufacturing Marvels Highlights Why EZAutomation Is a Force to Be Reckoned With

Watch EZAutomation's recent feature on the popular FOX Network series "Manufacturing Marvels" and discover what makes them a force to be reckoned with in industrial automation...